System 2: Permitted Standalone (3.2kW)
A full code-compliant standalone solar system with battery storage and 120V AC output. This is a capital improvement — a real asset with real inspections that powers real loads.
What You’ll Build
| Spec | Value |
|---|---|
| Array | 8 × 400W panels (3,200W STC) |
| Inverter | Off-grid inverter/charger |
| Battery | 5kWh LiFePO4 |
| Output | 120V / 20A GFCI-protected |
| Daily production | ~12–16 kWh (location-dependent) |
| Permit required | Yes — homeowner electrical permit |
| Inspections | Rough-in + final |
What You Can Power
This system produces enough energy to run significant loads through a dedicated circuit:
- Refrigerator/freezer (24/7 operation)
- Window A/C unit (during peak sun hours)
- Power tools in a shop or garage
- Well pump (intermittent loads)
- EV trickle charging (Level 1)
The 5kWh battery bank carries overnight loads or handles cloud cover. Think of this as a dedicated power station on your property — separate from the grid, separate from your utility bill.
The Permit Process
Homeowner Electrical Permits
In most states, homeowners can pull their own electrical permits for work on property they own and occupy. This is a fundamental property right. You don’t need to be a licensed electrician to wire your own system — you just need to meet code.
What to Expect
-
Application — Fill out the permit application at your local building department. Describe the project as “standalone solar PV system with battery storage, not connected to building electrical system.” Include your site plan showing panel location.
-
Plan review — The building department reviews your plans. For a standalone system, this is typically straightforward. Include your wiring diagram, equipment spec sheets, and site plan.
-
Rough-in inspection — Inspector verifies mounting, grounding, conduit runs, and wire sizing before you close up any junction boxes. Schedule this after mechanical installation is complete.
-
Final inspection — Inspector verifies labeling, overcurrent protection, grounding/bonding, and operational safety. System must be energized for this inspection.
Typical Timeline
- Permit application to approval: 1–2 weeks
- Build time: 2–3 weekends
- Inspections: Schedule within a few days of request
- Total: 3–6 weeks
System Design
Panels
| Parameter | Value |
|---|---|
| Module | 400W mono-PERC (any Tier 1) |
| Quantity | 8 |
| V_oc (typical) | ~41V |
| I_sc (typical) | ~13A |
| String configuration | 2 strings of 4 panels |
| V_oc per string | ~164V |
String voltage calculation (NEC 690.7):
The inverter’s MPPT input range determines your string length. With 4 panels per string:
- V_oc × 4 = ~164V (within typical 150–500V input range)
- Verify against your specific inverter’s MPPT voltage window
- Apply temperature correction factor per NEC 690.7 for your climate zone (cold temperatures increase voltage)
Inverter
| Parameter | Value |
|---|---|
| Type | Off-grid inverter/charger |
| Output | 120V / 60Hz split-phase capable |
| Continuous power | 3,000W minimum |
| Surge rating | 6,000W minimum |
| MPPT inputs | 2 (one per string) |
| Battery voltage | 48V nominal |
| Transfer switch | Built-in (if using backup grid) |
The off-grid inverter/charger is the brain of your system. It handles:
- MPPT — Maximum Power Point Tracking to optimize panel output
- Battery charging — Manages charge profiles for your LiFePO4 bank
- AC conversion — Produces clean 120V/60Hz sine wave output
- Load management — Handles surge loads and overload protection
Recommended units: Look for UL 1741 listed inverter/chargers from established manufacturers. Popular options include units from EG4, Sol-Ark, and Growatt in the 3kW–5kW range. Prices typically $800–$1,500.
Battery
| Parameter | Value |
|---|---|
| Chemistry | LiFePO4 (Lithium Iron Phosphate) |
| Capacity | 5kWh (100Ah at 48V) |
| Nominal voltage | 48V (51.2V actual) |
| Cycle life | 4,000–6,000 cycles |
| Depth of discharge | 90–100% |
| BMS | Built-in |
| UL listing | UL 9540A preferred |
LiFePO4 is the correct chemistry for stationary solar storage:
- No thermal runaway — inherently stable chemistry
- Long cycle life — 10–15 years at daily cycling
- Flat discharge curve — consistent voltage under load
- Drop-in ready — built-in BMS handles cell balancing
Grounding and Bonding
All metallic components must be bonded to a grounding electrode system:
- Equipment grounding conductor (EGC) — #6 AWG bare copper minimum, bonds all panel frames, racking, inverter chassis, and battery enclosure
- Grounding electrode — Ground rod (8’ minimum) or existing building electrode, per NEC 250
- Bonding jumper — Connects equipment ground to grounding electrode
- Panel frame bonds — Each panel frame bonded to racking with listed grounding clips (WEEB or equivalent)
Bill of Materials
Solar Array
| Item | Qty | Est. Cost |
|---|---|---|
| 400W mono-PERC panels | 8 | $600–$1,200 |
| Ground-mount racking system | 1 | $400–$800 |
| Panel grounding clips (WEEB) | 8 | $40–$80 |
| MC4 branch connectors (2-to-1) | 2 | $20–$40 |
| PV wire, 10 AWG (100ft) | 1 | $60–$100 |
Power Electronics
| Item | Qty | Est. Cost |
|---|---|---|
| Off-grid inverter/charger (3kW+) | 1 | $800–$1,500 |
| 5kWh LiFePO4 battery (48V) | 1 | $1,200–$2,000 |
| DC disconnect (fused, 150V+) | 1 | $60–$120 |
| DC breaker/fuses for strings | 2 | $40–$80 |
Electrical
| Item | Qty | Est. Cost |
|---|---|---|
| AC breaker panel (small, 4-space) | 1 | $30–$60 |
| GFCI breaker, 20A | 1 | $30–$50 |
| Ground rod (8ft copper-clad) | 1 | $15–$25 |
| Ground rod clamp | 1 | $8–$12 |
| #6 AWG bare copper (50ft) | 1 | $40–$60 |
| Conduit and fittings | — | $50–$100 |
| Junction boxes, connectors | — | $30–$60 |
| Wire (THHN, various gauges) | — | $50–$100 |
| Labels (NEC-required, engraved) | Set | $30–$60 |
Total Estimated Cost
| Scenario | Cost Range |
|---|---|
| Budget build | $3,500–$4,500 |
| Mid-range | $4,500–$6,000 |
| Premium | $6,000–$7,500 |
Wiring Topology
DC Source Circuit (Panels → DC Disconnect)
String 1: Panel 1 → Panel 2 → Panel 3 → Panel 4 ──┐
├── MC4 Y-connector → DC Disconnect
String 2: Panel 5 → Panel 6 → Panel 7 → Panel 8 ──┘
Wire sizing (NEC 690.8):
- I_sc per string: ~13A
- Continuous current adjustment: 13A × 1.25 = 16.25A
- Conduit fill adjustment: 16.25A × 1.25 = 20.3A
- 10 AWG PV wire — rated for 30A in conduit, satisfies NEC requirements
- Use PV wire (USE-2/PV rated) for exposed outdoor runs, THHN in conduit
DC Disconnect → Inverter
- Fused disconnect rated for string voltage × number of strings
- Short-circuit current rating must exceed available fault current
- NEC 690.15 requires a DC disconnect accessible to first responders
Battery Circuit
- 2 AWG minimum for 48V battery runs (verify with your inverter manual)
- Keep battery cable runs as short as possible
- Fused at battery with Class T or ANL fuse sized per inverter specs
- Battery disconnect switch accessible without crossing live conductors
AC Branch Circuit
Inverter AC Output → 20A GFCI Breaker → Receptacle(s)
- Standard 120V/20A branch circuit per NEC 210
- 12 AWG THHN in conduit
- GFCI protection required (NEC 210.8)
- Dedicated circuit — do not splice into existing building wiring
Labeling
NEC requires specific labels at specific locations. The inspector will check these. Use engraved or UV-resistant labels — not handwritten, not tape.
Required Labels
| Location | Label Text |
|---|---|
| DC disconnect | ”SOLAR PV DISCONNECT” — rated voltage and current |
| Inverter | ”SOLAR PV SYSTEM” — rated output, AC and DC specs |
| Battery enclosure | ”BATTERY STORAGE SYSTEM” — voltage, chemistry, capacity |
| AC output panel | ”SOLAR PV AC OUTPUT — NOT CONNECTED TO UTILITY” |
| Ground-mount array | ”WARNING: SOLAR PV ARRAY — ENERGIZED IN DAYLIGHT” |
| Each junction box | ”SOLAR PV” with conductor identification |
| Main service panel (if nearby) | “THIS BUILDING HAS A SEPARATE SOLAR PV SYSTEM” |
Step-by-Step Build
Phase 1: Planning and Permits
-
Site survey — Determine panel location (south-facing, minimal shading, ground mount preferred). Measure available area. You need roughly 180 sq ft for 8 panels.
-
Pull permit — Submit application to local building department. Include site plan, equipment spec sheets, and single-line wiring diagram.
-
Order equipment — While waiting for permit approval, order your panels, inverter, battery, and electrical materials. Lead times can be 1–3 weeks.
Phase 2: Mechanical Installation
-
Install ground-mount racking — Set posts/footings, level the racking rails. Follow manufacturer’s specs for spacing and tilt angle (latitude tilt is a good default).
-
Mount panels — Attach panels to racking with mid-clamps and end-clamps. Torque to manufacturer specs. Install grounding clips on each panel.
-
Run conduit — Install conduit from array to equipment location. Use outdoor-rated conduit (rigid or EMT) with proper fittings and weather heads.
Phase 3: Electrical — DC Side
-
Wire panel strings — Connect panels in series within each string. Use MC4 connectors (properly crimped, not the screw-on type). Verify string voltage with multimeter before proceeding.
-
Install DC disconnect — Mount fused disconnect between array and inverter. Land DC conductors on line side. Leave load side disconnected.
-
Run DC home runs — Pull PV wire through conduit from array to DC disconnect, then from disconnect to inverter location.
Phase 4: Rough-In Inspection
- Schedule rough-in — Call your building department. Inspector will verify: conduit fill, wire gauge, grounding conductors, mounting integrity, disconnect rating. Do not energize the system before this inspection.
Phase 5: Electrical — AC Side and Battery
-
Install inverter — Mount inverter per manufacturer’s specs (ventilation clearances, orientation). Land DC conductors from disconnect.
-
Install battery — Position battery per manufacturer clearance requirements. Connect to inverter with properly sized cables and fused disconnect.
-
Wire AC output — Install sub-panel or breaker enclosure. Wire GFCI breaker, run to receptacle(s). Install all required labels.
-
Commission system — Close DC disconnect. Verify inverter startup, battery charging, AC output voltage. Test GFCI trip.
Phase 6: Final Inspection
- Schedule final — Inspector will verify: labeling, GFCI operation, grounding/bonding continuity, overcurrent protection, voltage readings, overall workmanship. System must be energized.
Inspection Checklist
Use this checklist to self-inspect before calling for your official inspection:
Grounding and Bonding
- Ground rod installed and accessible
- Equipment grounding conductor connected to all frames and racking
- Bonding jumper from equipment ground to grounding electrode
- Panel grounding clips properly installed
Overcurrent Protection
- DC fuses/breakers sized correctly for string current
- Battery fuse sized per inverter manual
- AC GFCI breaker installed and functional
Wiring
- All connections torqued to spec
- No exposed conductors outside rated enclosures
- Conduit properly supported and sealed
- Wire gauge matches circuit requirements
Labeling
- All required labels in place (see labeling section)
- Labels are engraved or UV-resistant
- Labels legible and permanently attached
Safety
- DC disconnect accessible and operational
- Battery disconnect accessible
- GFCI trips on test
- No tripping hazards on conduit runs
Documentation
- Permit posted at job site
- Equipment spec sheets available for inspector
- Single-line diagram available
- Photos of covered work (rough-in)
Safety
This system operates at voltages that can injure or kill. Treat it with the same respect as any electrical system.
- DC voltage is always present when panels are exposed to light. You cannot turn off the sun. Use opaque covers on panels when working on DC circuits.
- Battery banks store significant energy. A short circuit across battery terminals can produce thousands of amps and cause arc flash. Always install and use the battery disconnect.
- Work on one circuit at a time. Verify de-energized state with a multimeter before touching any conductor.
- Wear appropriate PPE — insulated gloves rated for the voltage, safety glasses, closed-toe shoes.
- Never work alone. Have someone nearby who knows where the disconnects are and how to call 911.
What’s Next
After this system is running:
- Monitor your production — Track daily kWh output vs. expectations
- Calculate your actual payback — Use the Rate Calculator to determine your real per-kWh grid cost
- Consider expansion — Adding panels or battery capacity to an existing system is straightforward once the infrastructure is in place
- Share what you learned — The best way to break the utility monopoly is to show your neighbors it works